Trojan OMS

Overview

Trojan’s OMS range of oil filtering equipment provides transformer owners with a safe, cost-effective, and portable solution for filtering oil on energised transformers.

The Trojan OMS is highly effective at reducing dissolved moisture in the oil and transformer insulation and improving oil dielectric strength. An added benefit: by simply changing the type of media used, the OMS can also reduce the level of acidity in the transformer.

Trojans’ OMS systems are designed for safe online, unattended operation on transformers of all sizes in any location.

Description

Moisture assessment and removal

The Trojan OMS uses highly adsorbent media to remove moisture down to very low levels on energized transformers. Different media options are available, including loose media or filter cartridges.

The Trojan OMS system has the capacity to remove a large quantity of water from a transformer before saturation of the adsorbent media in its filter cylinders, where a specific grade of molecular sieve bead is used which is able to absorb a high percentage of its own structure in moisture without altering the DGA profile of the oil.

The OMS range can be manufactured to any number of columns and configured to use either filter elements or loose media.

Processing lower oil volumes

The Trojan OMS is a molecular sieve type water removal system that is designed to be used whilst the transformer is online & in service. It continuously removes water from the transformer oil and paper insulation, a process that not only reduces the rate of ageing, but will improve the dielectric strength of the insulation, increase its reliability and the operational lifespan of the transformer.

Highly portable oil filtering

The water molecules chemically bond to the molecular sieve material contained in the systems filter cylinders as the oil is pumped through the filter media. The total volume of molecular sieve material required in the system can vary between users, based on the respective oil volumes to be processed.

As a result, the system can be manufactured to suit.

The Trojan OMS filter columns are configured to use molecular sieve material in two different forms. Either of the following can be used, depending on individual customer preferences:

  • Loose Fill – Approx 35 kgs / 77 lbs of molecular sieve material per column.
    • Benefits: More adsorbent capacity, lower cost per gallon of moisture removed, longer duration until media becomes saturated, more cost effective.
  • Filter Elements – 4 filter elements, totalling 26 kgs / 57 lbs molecular sieve per column.
    • Benefits: quick & easy to replace.

Each configuration can be manufactured to contain any number of columns. The OMS – Cart offers users even greater portability & manoeuvrability than the standard version of the OMS.

The OMS-Cart is the perfect system for use on transformers located in very difficult to access locations with restricted access or mobility, which can include:

  • underground vaults;
  • inside small buildings;
  • high rise buildings;
  • Shopping centres.

Features

  • Effective removal of moisture on energized transformers
  • Highly portable unit that can be easily rotated between transformers
  • Designed for long term unattended operation on energized power transformers
  • An adsorbent based system using proven molecular sieve media with large adsorbent capacity
  • Two (2) selectable online oil treatment cycles (water in Oil Analysis; moisture removal)
  • Simple, safe and easy to follow HMI led process for commissioning, treatment program selection and drain cycles
  • PLC controlled with HMI interactive screen
  • Multiple interlocked safety cut-outs automatically shut down and isolate the system from the transformer
  • Speed control
  • Remote communications optional
  • Single or three Phase options; various voltages

Benefits

  • Extends the natural life of the transformer by reducing moisture in the insulation down to very low levels
  • No effect on oil DGA
  • No requirement to take outages at any stage (working clearances excepted)
  • Low ongoing cost of use – minimal consumables and labor requirements
  • Improves the oil and cellulose dielectric
  • Reduce total moisture issues across a large number of transformers

Specifications

OMS OMS200
Flow Rate (LPH / GPH) Variable: 350 / 92 max
Number of Filter Tanks 2
Media Capacity (kg / lbs 80 / 176
Moisture reduction to ≤ 2ppm
Particulate Reduction 1 μm
Manufacture Material Stainless steel
PLC control with HMI Yes
Water in oil sensors x 2: Inlet & Outlet
Safety Hose package Yes
Remote communications package Optional
Dimensions
L (mm / inches) 800mm / 31"
W (mm / inches) 860mm /34"
H (mm / inches) 1400mm / 55"
   
Weight (kg / lbs) 450 / 992
 
Power Supply
Phases Single / Three
Voltage As requested
Hz 50 / 60
   
Mounting: Stand or Trailer
Acidity Reduction Yes: Different media selection
Larger sizes / flow rates? Yes